Vue de la page 80
DC Module Remote Programming ReFlex Power™ Programming Manual
M380056-03 Rev L 77
Table 3-7. Group Pulse Function
The following section provides various List and Trigger examples for
synchronizing multiple modules.
L
IST
M
ODE
E
XAMPLES
1. Generate a 1 Volt saw tooth waveform on a 12 volt output to
simulate AC rectification ripple for 2.5 seconds.
LIST2:LABEL3
LIST2:RAMP:VOLT 13.0, 12.0, 8.33333e-3
LIST2:LOOP 299, LABEL3
2. Trigger example: synchronize multiple Modules, 1 & 4.
LIST1:START "TRIGTEST" // start LIST on module 1
TRIG1:INP A // set backplane line A as trigger input
SOUR1:VOLT 0.0 // set initial voltage to 0
SOUR1:CURR 1.0 // set current
OUTP1:STAT 1 // turn supply on
LIST1:LABEL0 // label allows the segment to be repeatable
LIST1:TRIG A, WAIT // wait for 1st trigger
SOUR1:VOLT 15.0 // program voltage
LIST1:TRIG A, WAIT // wait for 2nd trigger
LIST1:TRIG A, WAIT // wait for 3rd trigger
LIST1:TRIG A, WAIT // wait for 4th trigger
SOUR1:VOLT 0.0 // program voltage to 0
LIST1:LOOP 1, LABEL0 // loop once to repeat the sequence
OUTP1:STAT 0 // turn off supply
LIST1:END // end the LIST
LIST1:STORE // store the list
LIST4:START "TRIGTEST" // start LIST on module 4
TRIG4:INP A // set backplane line A as trigger input
SOUR4:VOLT 0.0 // set initial voltage to 0
SOUR4:CURR 5.0 // set current
OUTP4:STAT 1 // turn supply on
Pulse
Module
Function
1 DC1 DCV1 output to 5 V
2 DC1 and DC2 DCV1 to 10V and DCV2 to 5V
3
DC2
IDC2 to 1.2A and 5.5 volts
4 DC1, DC2 All outputs off
5 DC3 DCV3 to 12V and 2.0A
6 DC3 DC3 off