Ametek ReFlex Programming Manual Manuel d'utilisateur Page 133

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 134
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 132
Fixed Power DC Remote Programming ReFlex Power™ Programming Manual
M380056-03 Rev L 129
6.7
STATUS COMMANDS
6.7.1 STATUS
SCPI
C
OMMAND
S
UMMARY
STATus<n>
:MODule
:ENABles <0+NR1>
:ENABles?
:FAULts?
:HWREV?
6.7.2 STATUS
SCPI
C
OMMAND
R
EFERENCE
Command
Description
STATus<n>
STATUS subsystem of commands..
:MODule
:ENABles<0+NR1>
Enable supervisory faults, see Table
6-2
. Same
Table describes Fault bits.
:ENABles?
Query the enabled supervisories
:FAULts?
Query the supervisory faults.
:HWREV?
Returns Module type and Hardware Revision
Table 6-2. Fixed Power Faults and Enable Register
Bit
Hex Value
Mnemonics
Description
0 0x00000001 P5VF Plus 5 Volt Fault
1 0x00000002 M5VF Minus 5 Volt Fault
2 0x00000004 P15VF Plus 15 Volt Fault
3 0x00000008 M15VF Minus 15 Volts Fault
4 0x00000010 OTP Over Temperature Fault
5 0x00000020 5VSNSF 5 Volt House Keeping Sense Fault
6 0x00000040 12VSNSF 12 Volt House Keeping Sense Fault
7 0x00000080 PWROKF Power Ok Fault
6.8
SYSTEM COMMANDS
6.8.1 SYSTEM
SCPI
C
OMMAND
S
UMMARY
SYSTem
:ERRor?
6.8.2
SYSTEM
SCPI
C
OMMAND
R
EFERENCE
Command
Description
SYSTem
SYSTEM subsystem of commands.
:ERRor?
Returns the last
error logged in the Error/Event Queue. The message,
“0, No error”, is returned if there are no errors.
Vue de la page 132