ReFlex Power™ Programming Manual AC Module Remote Programming
100 M380056-03 Rev L
4.8
OUTPUT SCPI COMMANDS
4.8.1 OUTPUT
SCPI
C
OMMAND
S
UMMARY
OUTPut<n>
:STATe <bool>
:STATe?
:AUXRelay <bool>
:AUXRelay?
:ISOlation?
:SENSe?
4.8.2 OUTPUT
SCPI
C
OMMAND
R
EFERENCE
Command
Description
OUTPut<n>
OUTPUT subset of SCPI commands.
:STATe <bool>
Sets the output On or Off. Arguments are 1/ON, or 0/OFF.
:STATe?
Returns the state of the supply, 1 = On, and 0 = Off.
:AUXRelay <bool>
Set the Auxiliary Relay to open or close. 1= close ,and 0 = open.
Note: AUX Relay can be manipulated only when the output is On, and
output signal frequency is set within 350 - 1000 Hz range.
:AUXRelay?
Query the state of the Auxiliary relay
:ISOLation?
Query the state of the Isolation relay.
:SENSe?
Query the state of the Sense relay.