Features and Specifications
Rear Panel Connectors and Switch
22 Operating Manual for XHR Series Power Supply
Wiring
For lowest noise performance, make connections to the J2 connector with either
individually or group shielded 18-22 AWG (0.3-0.8 mm
2
) wire. Maintain the shield
to within 1.5in. (40 mm) of the end of each wire. Strip 0.26.in (6.5 mm) of insulation,
insert into the correct terminal, and tighten the wire clamp. You must ground the
shield(s) to the power supply chassis with a connection less than 1.5.in (40 mm)
long.
WARNING
There is a potential shock hazard at the output and J2 terminals when using a
power supply with a rated output greater than 40 V. Use load wiring with a
minimum insulation rating equivalent to the maximum output voltage of the
power supply. For example, select TEW-105, 105 °C, 600 V wiring for use with a
600 V, 1.7 A model power supply