Ametek 2120 PLC Interface Module Manuel d'utilisateur Page 46

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 64
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 45
42
Installation and Programming Manual
Chapter 4: Programming
Analog output channel 2 is programmed using the same basic sequences except with the function
numbers noted below. Remember that the X shown in the function number represents the slot in
which the analog output board is installed in the Interface Module chassis.
Analog Output Channel 2 - Function numbers
A) Select analog output based on position or velocity
Function No. X07
B) Select voltage or current output
Function No. X10
C) Scaling analog output
- Select minimum position/velocity value
Function No. X08
- Select analog output value to be linked to minimum position/velocity value
Function No. X11
- Select maximum position/velocity value
Function No. X09
- Select analog output value to be linked to maximum position/velocity value
Function No. X12
Analog output channel 1 will now provide a 2 to 8 VDC output as RPM increases between 500
and 2000 RPM. RPM values below 500 RPM will result in a 2 VDC analog output. RPM values
above 2000 RPM will result in an 8 VDC output.